ESP CONTROLLER
- Home
- EasyCon-I-ESP CONTROLLER
EasyCon-I ESP
The proposed general features and specification of Electrostatic Precipitator
(ESP) Controller for Single Phase TR control operation as below
Features:
- Spark rate control
- Back Corona Detection
- Semi pulse operation for ODD cycles
- Internal Timer based Motorized 3 Rapper Controls
- Modes of Operation
- -Constant Current Output mode
- -Load Status (External load dependent) mod
-
Monitoring Parameters
- -Input Voltage (VP)
- -Input Current (IP)
- -Output Voltage mean (KVa)
- -Output Voltage Peak (KVp)
- -Output Voltage Trough (KVt)
- -Output Current Mean (IS)
- -Mains Frequency (Hz)
- -Output KW
- -Output KWH
- -Firing angle (deg.)
Input Supply:
- 24V AC +-10% @ 2A, 50/60Hz 5%, Single Phase
Human to Machine Interface (HMI):
- Alphanumeric LCD display (16 x 4) for displaying the various parameter settings, actual status, alarms, trips etc.
- Matrix Keypad (6 x 3) with 16 keys for setting parameter values
Analog Inputs
- Input Voltage 0-5VAC@rated 415VAC (VP)
- Input Current (IP)
- Output Voltage mean 0-400uA@ rated kv peak (VS)
- Output Current mean 0-1V@ rated mA (IS)
Analogue Outputs:
- 0-20mA or 4-20mA for Output Current (IS)
- 0-20mA or 4-20mA for Output Voltage (KV)
Digital Inputs
Potential free (NO) contacts for following digital inputs- Contactor On
- Load status 1
- Rapper Reduction
Alarm Input
Potential free (NO) contacts for the following Alarm inputs:
- TR Temperature
- Top Float / Oil level low
- Rapper 1 feedback
- Rapper 2 feedback
- Rapper 3 feedback
Trip Input
Potential free (NC) contacts for the following trip inputs:
- TR Temperature – Trip
- Bottom Float / TR Pressure High
- SCR Temperature high
- HT Interlock
- Overload Trip
Digital Output
Potential Free (NO) Relay contacts (24VAC @5A Max) are available for the following digital outputs:
- HT ON
- HT OFF
- Local / Remote HT ON
- Rapper 1
- Rapper 2
- Rapper 3
- Buzzer
PWM Port Output
Digital signals for single phase TR:
- Positive SCR ignition
- Negative SCR ignition
Internal Software Alarm / Trips
Internal software alarms and trips:
- AC Current High Trip
- Synchronization Fail Trip
- DC Under Voltage Trip
- DC Overvoltage Trip
- Contactor Error Trip
Communication Interface
RS 485 Port with RTU MODBUS Protocol:
- Baud rate: 9600bps, 19200bps, 38400bps (Selectable through keypad only)